Inovance MD500 Inverter
The Inovance MD500 is a compact, high-performance AC inverter designed for precise motor control and energy efficiency in industrial automation.
Ideal for packaging, printing, and HVAC, it offers fast response, strong protection, and flexible communication.
- Compact design for easy cabinet installation
- Fast response for accurate torque and speed control
- Full protection against overvoltage, overcurrent, and overheating
- Flexible control with V/F, Vector, and PM motor modes
- Built-in Modbus RTU / EtherNet/IP communication
Delivering reliability and performance, the MD500 ensures stable operation and reduced downtime across diverse automation systems.

🧠 How the Inovance MD500 Reports Errors
When a fault occurs, the drive automatically stops output to protect the motor and displays an “ErrXX” code on its keypad. The TUNE/TC LED flashes, and a trip log is saved.
| Type | Description | LED Behavior | Recovery |
|---|---|---|---|
| Fault (Err) | Stops drive output immediately. | LED flashes | Must be manually reset. |
| Warning (AL) | Alerts of an issue; continues running. | LED steady | Correct parameter or cooling. |
| Protection Stop | Stops output; self-resets after condition clears. | — | Auto reset when safe. |
📘 Tip: Access F9-14 to F9-44 to view the last three fault logs (including voltage, current, and status at the time of failure).
🔁 How to Reset Faults
| Method | Action | Use Case |
|---|---|---|
| Panel Reset | Press STOP/RES if F7-02 = 1. | Normal reset after fix. |
| DI Terminal Reset | Assign DI terminal function = 9 (Fault Reset). | Remote reset from PLC. |
| Power Cycle | Turn OFF then ON. | Clears latched faults. |
| Communication Reset | Set F0-02 = 2, write “7” to address 2000H. | Remote monitoring systems. |
🧾 Inovance MD500 Error Codes and Solutions
Below is the comprehensive list of Inovance MD500 error codes (Err01–Err62), organized with fault names, causes, and corrective actions — extracted from the official manual and restructured for field use.
| Error Code | Fault Name | Possible Causes | Solutions |
|---|---|---|---|
| Err02 | Overcurrent during acceleration | Ground fault, short circuit, no auto-tuning, accel too short, wrong current limit, external interference. | Check motor wiring; perform auto-tuning; increase accel time; enable current limit (F3-19 = 1); adjust F3-18 (120–150%), F3-20 (20–40). |
| Err03 | Overcurrent during deceleration | Short circuit, no auto-tuning, decel too short, missing brake resistor, interference. | Check cables; perform auto-tuning; install braking resistor; extend decel time. |
| Err04 | Overcurrent at constant speed | Ground fault, improper torque boost, undersized drive, interference. | Inspect motor leads; reduce F3-01 torque boost; upgrade drive class. |
| Err05 | Overvoltage during acceleration | Input voltage high, short accel time, regenerative energy. | Normalize supply; enable voltage limit (F3-23 = 1); install brake resistor; increase accel time. |
| Err06 | Overvoltage during deceleration | Short decel, external force, missing resistor. | Enable voltage limit; increase decel time; install braking resistor. |
| Err07 | Overvoltage at constant speed | External load feedback energy. | Install braking resistor; tune F3-22 (700–770 V); adjust F3-24 (30–50). |
| Err08 | Pre-charge resistor fault | Bus voltage fluctuation. | Contact Inovance or agent. |
| Err09 | Undervoltage | Power dip, supply out of range, rectifier fault. | Enable ride-through (F9-59 ≠ 0); stabilize input power; replace rectifier if faulty. |
| Err10 | Drive overload | Heavy load or locked rotor. | Reduce mechanical load; use larger-rated drive. |
| Err11 | Motor overload | Wrong F9-01 setting or excessive torque. | Set F9-01 correctly; reduce load. |
| Err12 | Input phase loss | Missing phase or rectifier damage. | Inspect input R/S/T; check fuses; replace rectifier if needed. |
| Err13 | Output phase loss | Broken motor winding, bad cable, or IGBT fault. | Check continuity; replace motor or drive board if unbalanced. |
| Err14 | IGBT overheat | High temperature, blocked fan, sensor failure. | Clean vents; replace fan or sensor; reduce ambient temperature. |
| Err15 | External fault | DI input or virtual I/O triggered. | Reset after clearing input (F8-18/A1 settings). |
| Err16 | Communication fault | Wrong protocol, cable noise, Modbus setting mismatch. | Verify F0-28, Fd-group; check cable shielding. |
| Err17 | Contactor fault | Relay or lightning board failure. | Replace defective boards or contactor. |
| Err18 | Current detection fault | Hall sensor failure. | Replace hall sensor or drive board. |
| Err19 | Auto-tuning fault | Wrong motor data, encoder issue. | Enter correct motor parameters; verify encoder wiring. |
| Err20 | Encoder fault | Wrong type, damaged encoder, wiring error. | Correct encoder setting (F1-27); check PG card; replace encoder. |
| Err21 | EEPROM fault | Memory failure. | Replace main control board. |
| Err23 | Ground short circuit | Motor insulation failure. | Replace cable or motor; perform megger test. |
| Err26 | Running time limit reached | Runtime limit triggered. | Reset via parameter initialization. |
| Err27 / Err28 | User-defined faults | DI/virtual I/O triggered. | Reset; verify user logic settings. |
| Err29 | Power-on time exceeded | Accumulated time limit reached. | Reset runtime counter. |
| Err30 | Load loss | Output current < F9-64. | Reconnect load; adjust F9-64/F9-65. |
| Err31 | PID feedback lost | Feedback signal below FA-26. | Check PID sensor; correct FA-26 threshold. |
| Err40 | Pulse-by-pulse current limit | Heavy load or undersized drive. | Reduce torque; use higher-rated drive. |
| Err41 | Motor switchover fault | Switched motor during run. | Switch only when stopped. |
| Err42 | Speed error | Encoder data mismatch, no auto-tuning. | Perform auto-tuning; check F9-69/F9-70 values. |
| Err43 | Overspeed | Encoder/parameter mismatch. | Perform auto-tuning; adjust F9-67/F9-68. |
| Err45 | Motor overtemperature | High temperature or loose sensor wiring. | Tighten connections; improve cooling; reduce carrier frequency. |
| Err51 | Braking unit overload | Resistor too small or frequent decel. | Replace with larger resistor; extend decel time. |
| Err62 | Braking circuit short | Braking IGBT damaged. | Replace IGBT; contact Inovance. |
🧮 Parameter Groups to Check
| Parameter Group | Function | Notes |
|---|---|---|
| F3-xx | Voltage and current limit | Adjust F3-18, F3-22, F3-24 for stall and voltage protection. |
| F8-xx | DI/DO logic setup | Check F8-18 for restart permissions. |
| F9-xx | Protection and monitoring | F9-59 = ride-through; F9-64–F9-70 = load and speed error detection. |
| FA-xx | PID control parameters | Adjust FA-26 for feedback level detection. |
⚠️ Safety Reminder: Before inspection or resetting, disconnect power for at least 10 minutes to allow DC bus capacitors to discharge.
🧰 Quick Troubleshooting Flow
- Read code on display (e.g., “Err06”).
- Check fault log (F9-14 – F9-44).
- Verify motor and wiring for shorts, phase loss, or overheating.
- Confirm parameters (F3, F8, F9) are within safe ranges.
- Fix mechanical causes (load, fan, environment).
- Reset drive via keypad or DI input.
- Run test to confirm stability.
🔧 Preventive Maintenance
- Inspect fans, vents, and heatsinks quarterly.
- Use shielded cables and grounded wiring to minimize EMI.
- Perform motor auto-tuning after replacement or rewiring.
- Back up parameters before firmware or hardware changes.
- Monitor F9-05 (DC bus voltage) and U4-xx (lifetime counters) regularly.
✅ Summary
The Inovance MD500 error codes system provides a structured, intelligent diagnostic method to keep your VFDs healthy.
From simple faults like Err02 (Overcurrent) to complex control issues like Err20 (Encoder fault), each code reflects a specific hardware or operational problem — and offers clear guidance for resolution.
By learning these codes and keeping your parameters optimized, you can dramatically reduce unplanned downtime and extend the life of your Inovance MD500 drive.
Still Struggling? Let Our Experts Assist You
Facing persistent machine issues? Our team of technical experts is here to help. At Jota Machinery, we provide tailored solutions and ongoing support to keep your production running smoothly—no matter the challenge.