Mitsubishi QCPU

The MELSEC-Q series QCPU provides high-performance processing, stable system control, and flexible system configuration for medium to large-scale industrial automation.
It is designed for applications requiring high reliability, large program capacity, and multi-CPU system support, such as packaging lines, printing systems, converting equipment, and complex production machinery.

Key Features

  • High-performance CPU architecture for fast instruction execution
  • Support for multiple CPU systems and distributed control
  • Large memory capacity for complex programs and data processing
  • Advanced diagnostics and system protection functions
  • Flexible communication and control with intelligent modules and networks

The QCPU series enables stable system operation, reliable multi-CPU coordination, and efficient troubleshooting in demanding industrial environments.

inovance

Find the Error Code List and Troubleshooting

1️⃣ Version & Compatibility Errors

Error CodeError NameCauseSolution
2000UNIT VERIFY ERROR QCPU function version A is used in a multiple CPU system. Multiple CPU systems require function version B or later. Replace all CPUs with function version B or later, then power cycle the system.
2125SP.UNIT LAY ERROR Multiple CPU configuration detected while using unsupported CPU function versions. Upgrade CPU modules to a compatible function version and recheck system configuration.
7010MULTI EXE. ERROR Mixed CPU function versions (version A and version B) are installed in the same multiple CPU system. Standardize all CPUs to the same function version (version B or later) and restart the system.

2️⃣ Module Layout & Hardware Limit Errors

Error CodeError NameCauseSolution
2124SP.UNIT LAY ERR The number of mounted I/O modules exceeds the maximum allowed for the base unit in a multiple CPU system. Reduce the number of I/O modules to comply with the base unit specification, or add an extension base.
2150SP.UNIT VER.ERR A CPU other than CPU No.1 is assigned as the control CPU for a communication module (e.g. serial or network module). Set CPU No.1 as the control CPU in PLC parameters, then restart the system.

3️⃣ Parameter & Configuration Errors

Error CodeError NameCauseSolution
3009PARAMETER ERROR Different control CPUs are assigned to AnS/A series modules on the same base unit in a multiple CPU configuration. Set the same control CPU for all AnS/A series modules on the base, then write parameters and restart the system.
3012PARAMETER ERROR Multiple CPU parameters are inconsistent between CPUs (consistency check failure at startup). Align the multiple CPU settings across all CPUs (system configuration, PLC count, assignments), then reset CPU No.1.
3015PARAMETER ERROR Parameter inconsistency or unsupported parameter combination within the multiple CPU system (startup parameter validation failure). Correct the related parameters to a supported combination, write parameters to all CPUs, then reset CPU No.1.

4️⃣ Access & Shared Memory Errors

Error CodeError NameCauseSolution
2110SP.UNIT ERROR An instruction attempted to access a CPU module that is not physically mounted in the multiple CPU system. Verify CPU mounting position and slot configuration, then correct the access instruction.
2114SP.UNIT ERROR Invalid read or write access to the local CPU shared memory using a restricted instruction in a High-Performance or Process CPU. Use permitted instructions (such as S.TO) or change CPU type to Universal model if required.
2115SP.UNIT ERROR Writing to the shared memory area of another CPU using an unsupported instruction. Do not write directly to other CPUs’ shared memory. Use auto-refresh or approved inter-CPU data exchange methods.
2116SP.UNIT ERROR Writing to the buffer memory of an intelligent function module that is controlled by another CPU. Reassign the control CPU for the module or restrict access to read-only operations.
4102OPERATION ERROR Link direct device was used to access a module that is not controlled by the local CPU. Access only modules controlled by the local CPU and revise device addressing accordingly.

5️⃣ Execution & Instruction Load Errors

Error CodeError NameCauseSolution
4107OPERATION ERROR The number of unprocessed multiple-CPU or motion-related instructions exceeds the allowable limit (33 or more queued). Limit the number of simultaneously executed instructions to 32 or fewer. Add interlocks or sequence control to stagger instruction execution.

6️⃣ System STOP / Multi-CPU Control Errors

Error CodeError NameCauseSolution
7000MULTI CPU DOWN A reset or STOP-level error occurred in a CPU other than CPU No.1, or “All station stop” is enabled during a major error. Identify and eliminate the original error cause, then reset CPU No.1 or power-cycle the system.
7020MULTI EXE. ERROR A STOP error occurred in one CPU while “All station stop” is disabled, allowing the system to continue operating. Locate and correct the error in the affected CPU to prevent further system instability.

7️⃣ Error Code Summary (Quick Reference)

CategoryError CodesDescription
Version & Compatibility2000, 2125, 7010 Errors caused by incompatible or mixed CPU function versions in a multiple CPU system.
Module Layout & Hardware Limits2124, 2150 Errors related to exceeding base unit specifications or incorrect control CPU assignment.
Parameter & Configuration3009, 3012, 3015 Multiple CPU parameter inconsistencies detected during startup or configuration checks.
Access & Shared Memory2110, 2114, 2115, 2116, 4102 Illegal access to CPU shared memory, buffer memory, or modules controlled by another CPU.
Execution & Instruction Load4107 Excessive unprocessed multiple-CPU or motion instructions queued at the same time.
System STOP / Multi-CPU Control7000, 7020 STOP-level errors affecting overall multiple CPU operation and execution control.

8️⃣ Intelligent / Analog Module Errors (Typical)

StepActionEngineering Purpose
1Check CPU status and LED indicators Confirm whether the system is in RUN or STOP state and identify major fault conditions immediately.
2Open GX Works2 / GX Works3 diagnostics Access detailed error codes, error sources, and module-level diagnostics.
3Review Event History Identify the first error; subsequent errors are often secondary effects.
4Verify hardware configuration Check CPU arrangement, module layout, control CPU assignment, and wiring.
5Confirm multiple CPU parameters Ensure parameter consistency across all CPUs before attempting system restart.
6Correct root cause and reset CPU No.1 Multiple CPU systems require CPU No.1 to be reset after fault correction.

9️⃣ I/O Troubleshooting

ItemIncluded in This ListNot Included in This List
Error scope QCPU multiple CPU system errors documented in the QCPU User’s Manual (Multiple CPU System) FX, L, iQ-R series errors or single CPU system errors
Error type System STOP errors, configuration errors, parameter errors, access violations Instruction-level runtime errors (C**** / F**** series)
Source CPU-level and system-level diagnostics Intelligent module–specific error tables (analog, motion, network)
Tool dependency Errors confirmed via GX Works2 / GX Works3 diagnostics Compile-time or online-edit tool warnings only
Completeness All error codes explicitly listed in the Multiple CPU System manual A theoretical “complete Mitsubishi error list”

Still Struggling? Let Our Experts Assist You

Facing persistent machine issues? Our team of technical experts is here to help. At Jota Machinery, we provide tailored solutions and ongoing support to keep your production running smoothly—no matter the challenge.

Fix It with Jota

Contact Information

  • No. 68, Shaojing Road, Economic Development Zone, Kunshan City, Jiangsu Province, China
  • +86 18151140150
  • admin@jotamachinery.com

Scroll to Top